Skip to main content

Digital Pulse Determination of High-Current Shunts Frequency Response

Anton Zarevich, Sergey Muravyov, Elena Bedareva

Abstract

In the paper a digital signal processing method for measuring frequency response function of highcurrent shunt are described. This is based on a joint digital processing of the input short pulse signal and a corresponding output. In order to measure the frequency response function, a short current pulse is applied to the shunt input; input and output signals of the shunt are recorded in a digital oscilloscope memory; then spectra of these two signals are computed. Amplitude and phase responses are determined by the arithmetic ratio of spectral components of the input and output signals at appropriate frequencies. For this purpose, an algorithm has been proposed and investigated.

Keywords
current shunt, dynamic behaviour, fourier transform
Download
IMEKO-TC4-2013-120.pdf
DOI
-
IMEKO TC
TC4 - Measurement of Electrical Quantities

Event details